NOTES:
1. The climatic curve can be applied to both the delivery temperature (water adjustment) and the am-
bient air (only if the specific air probe supplied has been installed); you are advised, however, to use
the check on the delivery temperature.
2. The climatic curves can only be applied to heating and cooling, not to domestic hot water produc-
tion.
Weather depend (1/3)
Weather depend: Off
Upper AT Heat: 25°C
Lower AT Heat: -20°C
Upper WT Heat: 55°C
Lower WT Heat: 40°C
3 4
1
2
4.7. Setting the automatic setting compensation on the basis of external air (Weather depend)
After accessing the “Weather depend” function, you
can set all the parameters related to offsetting work
set-points in accordance with variations in outside air
temperature. The following keys are used to navigate
this menu:
(
1
) Move back to the previous page
(
2
) Move on to the next page
(
3
) Go back to the higher level menu
(
4
) Go back to the main page (Home)
To activate this function, click on the “Weather de-
pend“ label (the first item on the first page of the func-
tion). Select “On and then confirm with “OK”.
Subsequently, the values for the various parameters
that make up climatic curves will be set; these param-
eters represent the curves that the system will use to
change the set automatically on the delivery temper-
ature or the ambient air temperature (if an air-based
control has been set, using the specific accessory air
probe) to both hot and cold:
Weather depend
On
Off
OK Cancel
Upper AT Heat
Range: 10~37°C Default: 25°C
+
-
25°C
OK Cancel
To set values for each parameter to create the climatic
curves, click on the label of the parameter in question
and set the desired value using the "+" or "-" keys to
enter a value within the permitted range. After setting
the value, press “OK” to confirm and return to the high-
er level.
Lower AT Upper AT
Upper WT
Upper RT
Lower WT
Lower RT

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC HMI Series and is the answer not in the manual?

AERMEC HMI Series Specifications

General IconGeneral
BrandAERMEC
ModelHMI Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals