6. The timer for hot water production will only be available if the operating mode envisages hot water
production.
7. The timer function will only work once. If you want to use it again, you must re-set it.
8. The timer is deactivated if the unit is manually switched on before the timer start time.
9. If the relative function is activated (paragraph 8.3), the value of this parameter will be stored in the
memory and automatically reset after any possible voltage failure.
10. The default value for this function is “Off”.
After accessing the Temp. timer function, you can
set programmed variations of the water delivery set-
point (this set-point will depend on the currently ac-
tive operating mode). The function can be activated
or deactivated by clicking on the Temp. timer” label;
click on the “Period 1” label to specify the time at
which the water delivery set-point is to be changed,
setting it to the value specified in the “WOT-heat 1”
parameter (which when clicked will display a numeric
keypad to change its value). Set “Period 2” with related
“WOT-heat 2” in the same way.
Click on the labels for the delivery temperature pa-
rameters to display a numeric keypad (with an indica-
tion of the range of permitted values) which you can
use to enter the required values.
00 00
01 01
02 02
23 59
22 58
Temp. timer
Temp. timer: Off
Period 1: 00:00
WT heat 1: 45°C
Period 2: 00:00
WT heat 2: 45°C
NOTES:
1. Press the icon to save and implement the setting.
2. This function is not available if DHW mode is set.
3. To activate this function, the unit must be enabled.
4. The time bands apply to the current day only.
5. If “Weekly timer, “Preset mode“, “Clock timer”, Temp. timer“ are set at the same time, priority is given
to the last one of these to be set.
00 00
01 01
02 02
23 59
22 58
Min: 25 Max: 60
X
0
1 2 3
4 5 6
7 8
0 -
9
OK
00 00
01 01
02 02
23 59
22 58
Temp. timer
Temp. timer: Off
Period 1: 00:00
WT heat 1: 45°C
Period 2: 00:00
WT heat 2: 45°C
4.12. Setting programmed setting changes on system water delivery (Temp. timer)