HEATING
WRL-H VERSION
POWER
SUPPLY
U.M.
025H 030H 040H 050H 070H 080H 100H 140H 160H
HEATING MODE 0/-3 - 30/35 °C “FROST”
Heating capacity °
230V-1
kW
6.28 8.44 10.17 - - - - - -
400V-3N 6.23 7.90 10.11 13.26 17.29 20.51 26.52 34.58 41.16
Total input power °
230V-1
kW
1.56 1.95 2.36 - - - - - -
400V-3N 1.56 1.82 2.31 3.00 3.92 4.67 6.00 7.80 9.35
Total input current °
230V-1
A
8.33 10.35 12.46 - - - - - -
400V-3N 3.85 3.85 5.31 6.49 8.32 9.69 12.28 15.94 18.74
Condenser water flow rate °
230V-1
l/h
1079 1451 1750 - - - - - -
400V-3N 1072 1359 1739 2280 2974 3527 4561 5948 7079
System side pressure drops °
230V-1
kPa
13 16 19 - - - - - -
400V-3N 13 13 19 18 22 27 23 30 38
Evaporator water consumption °
230V-1
l/h
1502 2063 2484 - - - - - -
400V-3N 1489 1934 2481 3265 4254 5038 6529 8523 10122
Geothermicside pressure drops °
230V-1
kPa
31 39 45 - - - - - -
400V-3N 30 34 44 45 50 63 50 63 81
C.O.P. °
230V-1
-
4.04 4.32 4.30 - - - - - -
400V-3N 4.01 4.33 4.37 4.42 4.41 4.39 4.42 4.43 4.40
THE DATA DECLARED DO NOT CONSIDER PUMP CORRECTION.
Attention:
The data given have been calculated with 25% gycol.
13