32 Rockwell Automation Publication 1734-UM013C-EN-P - August 2010
Chapter 2 Safety Functions
I/O Status Data
In addition to I/O data, the module provides status data for monitoring the I/O
circuits. The status includes the following data, which can be read by the
controllers. Note that 1 = ON/Normal and 0 = OFF/Fault/Alarm:
Individual Point Input Status
Combined Input Status
Individual Point Output Status
Combined Output Status
Individual Test Output Status
Individual Output Monitor (actual ON/OFF state of the outputs)
Individual Point status indicates whether each safety input, safety output, or test
output is normal (normal status: ON, faulted status: OFF). For fatal errors,
communication connections may be broken, so the status data cannot be read.
Status bits are OFF in the controller data table when the connection is lost.
Combined status is provided by an AND of the status of all safety inputs or all
safety outputs. When all inputs or outputs are normal the respective combined
status is ON. When one or more of them has an error, the respective combined
status is OFF. This is known as the combined safety input status or combined-
safety output status.

Table of Contents

Other manuals for Allen-Bradley 1734-IB8S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1734-IB8S and is the answer not in the manual?

Allen-Bradley 1734-IB8S Specifications

General IconGeneral
BrandAllen-Bradley
Model1734-IB8S
CategoryControl Unit
LanguageEnglish

Related product manuals