28 1769-L32E, 1769-L35E CompactLogix Controller
Publication
1769-IN020-C-EN-P - July 2007
Use AutoFlash to Load Firmware
You can use AutoFlash to load firmware through a serial connection.
1. Mak
e sure the appropriate network connection is made before
starting.
2. Use
RSLogix 5000 programming software to create a controller
project.
This automatically launches AutoFlash.
3. Choose the catalog number of the controller and click Next.
4. Exp
and the network until you see the controller.
If the required network is not shown, first configure a driver
for the network in RSLinx software.
5. Cho
ose the controller and click Ok.
6. Choose the revision level to which you want to update the
controller and click Next.
7. T
o start the update of the controller, click Finish and then click
Yes.
After the controller is updated, the status dialog displays
Update complete.
8. Clic
k Ok.
9. T
o close the AutoFlash utility, click Cancel and then click Yes.