174 Rockwell Automation Publication 2080-UM002G-EN-E - March 2015
Appendix A Specifications
Micro850 24-Point Controllers
General Specifications – 2080-LC50-24AWB, 2080-LC50-24QWB, 2080-LC50-24QVB, 2080-LC50-24QBB
Attribute 2080-LC50-24AWB 2080-LC50-24QWB 2080-LC50-24QVB 2080-LC50-24QBB
Number of I/O 24 (14 inputs, 10 outputs)
Dimensions
HxWxD
90 x 158 x 80 mm
(3.54 x 6.22 x 3.15 in.)
Shipping weight, approx. 0.423 kg (0.933 lb)
Wire size 0.2…2.5 mm
2
(24…12 AWG) solid copper wire or
0.2…2.5 mm
2
(24…12 AWG) stranded copper wire
rated @ 90 °C (194 °F ) insulation max
Wiring category
(1)
2 – on signal ports
2 – on power ports
2 – on communication ports
Wire type Use Copper Conductors only
Terminal screw torque 0.4…0.5 Nm (3.5…4.4 lb-in.) using a 0.6 x 3.5 mm flat-blade screwdriver.
(Note: Use a handheld screwdriver to hold down the screws at the side.)
Input circuit type 12/24V sink/source (standard)
24V sink/source (high-speed)
Output circuit type Relay 24V DC sink (standard
and high-speed)
24V DC source (standard
and high-speed)
Power consumption 28 W
Power supply voltage range 20.4…26.4V DC Class 2
I/O rating Input 120V AC 16 mA
Output 2 A, 240V AC,
2A, 24V DC
Input 24V, 8.8 mA
Output 2 A, 240V AC
2A, 24V DC
Input 24V, 8.8 mA
Output 24V DC, Class 2, 1 A per point (Surrounding
air temperature 30 °C)
24V DC, Class 2, 0.3 A per point (Surrounding air
temperature 65 °C)
Isolation voltage 250V (continuous), Reinforced
Insulation Type, Output to Aux
and Network, Inputs to Outputs.
Type tested for 60 s @ 3250V
DC Output to Aux and Network,
Inputs to Outputs
150V (continuous), Reinforced
Insulation Type, Input to Aux
and Network.
Type tested for 60 s @ 1950V
DC Input to Aux and Network
250V (continuous), Reinforced
Insulation Type, Output to Aux
and Network, Inputs to
Outputs.
Type tested for 60 s @ 3250V
DC Output to Aux and Network,
Inputs to Outputs.
50V (continuous), Reinforced
Insulation Type, Input to Aux
and Network
Type tested for 60 s @ 720V
DC, Input to Aux and Network
50V (continuous), Reinforced Insulation Type, I/O to
Aux and Network, Inputs to Outputs.
Type tested for 60 s @ 720 V DC, I/O to Aux and
Network, Inputs to Outputs.
Pilot duty rating C300, R150
Insulation stripping length 7 mm (0.28 in.)
Enclosure type rating Meets IP20
North American temp code T4
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.