Rockwell Automation Publication 2080-UM002K-EN-E - March 2019 55
Wire Your Controller Chapter 4
Embedded Serial Port
Wiring
The embedded serial port is a non-isolated RS232/RS485 serial port which is
targeted to be used for short distances (<3 m) to devices such as HMIs.
See Embedded Serial Port Cables
on page8 for a list of cables that can be used
with the embedded serial port 8-pin Mini DIN connector.
For example the 1761-CBL-PM02 cable is typically used to connect the
embedded serial port to PanelView Component HMI using RS232.
Embedded Serial Port
Pinout table
Pin Definition RS-485 Example RS-232 Example
1 RS-485+ B(+) (not used)
2 GND GND GND
3 RS-232 RTS (not used) RTS
4 RS-232 RxD (not used) RxD
5 RS-232 DCD (not used) DCD
6 RS-232 CTS (not used) CTS
7 RS-232 TxD (not used) TxD
8 RS-485- A(-) (not used)
IMPORTANT
Do not connect the GND pin of the serial port to Earth/Chassis
Ground. The GND pin of the serial port is the DC common for the
Serial Port Communication signals and is not intended for Shield
Ground.
If the length of the serial cable is more than 3 meters, use an isolated
serial port, catalog number 2080-SERIALISOL.