MicroLogix 1200 Analog Output Module 17
Publication 1762-IN016B-EN-P - December 2005
Specifications
Analog Input Module - 1762-OF4 General Specifications
Specification Value
Dimensions
(H x W x D), Approx.
90 mm (3.54 in) x 40 mm (1.58 in) x 87 mm (3.43 in)
height including mounting tabs is 110 mm (4.33 in)
Approx. Shipping Weight
(with carton)
235 g (0.517 lb)
Storage Temperature -40 … 85 °C (-40 … 185 °F)
Operating Temperature 0 … 55 °C (32 … 131 °F)
Operating Humidity 5% to 95% non-condensing
Operating Altitude 2000 m (6561 ft)
Vibration Operating: 10 … 500 Hz, 5G, 0.030 in. max. peak-to-peak
Shock Operating: 30 g
Bus Current Draw (max.) 40 mA at 5V dc
165 mA at 24V dc
Analog Normal Operating Range Voltage: 0 … 10V dc
Current: 4 … 20 mA
Full Scale
(1)
Analog Ranges
(1) The over- or under-range flag comes on when the normal operating range (over/under) is exceeded. The module continues to
convert the analog output up to the maximum full scale range.
Voltage: 0 … 10.5V dc
Current: 0 … 21 mA
Resolution 12 bits (unipolar)
Repeatability
(2)
(2) Repeatability is the ability of the output module to reproduce output reading when the same controller value is applied to it
consecutively, under the same conditions and in the same direction.
±0.1%
Heat Dissipation 2.8 W
Output Group to System Isolation
30V ac/30V dc rated working voltage
(3)
(IEC Class 2 reinforced insulation)
type test: 500V ac or 707V dc for 1 minute
(3) Rated working voltage is the maximum continuous voltage that can be applied at the terminals with respect to earth ground.
Recommended Cable Belden 8761 (shielded)
Vendor I.D. Code 1
Product Type Code 10
Product Code 66