3-12 Programming and Parameters
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Basic Program Group (continued)
P110 [Decel Time 1] Related Parameter(s): P108, P109, t201, t202, A402, A410-A413
Sets the rate of deceleration for all speed decreases.
Values Default 10.0 Secs
Min/Max: 0.1/600.0 Secs
Display: 0.1 Secs
Maximum Freq
Decel Time
Decel Rate
=
Speed
0
Time
P105 [Maximum Freq]
P109 or A401
[Accel Time x]
P110 or A402
[Decel Time x]
0
Acceleration
Deceleration
P111 [Motor OL Ret] Related Parameter(s): P103
Enables/disables the Motor Overload Retention function. When Enabled, the value held in the motor
overload counter is saved at power-down and restored at power-up. A change to this parameter
setting resets the counter.
Options 0 “D
isabled” (Default)
1 “E
nabled”
P112 [Reset To Defalts]
Stop drive before changing this parameter.
Resets all parameter values to factory defaults.
Options 0 “I
dle State” (Default)
1 “R
eset Defaults” After the reset function is complete, this parameter will set
itself back to “0”.
Caus
es an F48 Params Defaulted fault.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 4M and is the answer not in the manual?

Allen-Bradley PowerFlex 4M Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 4M
CategoryController
LanguageEnglish

Related product manuals