Programming and Parameters 3-19
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Advanced Program Group
A401 [Accel Time 2] Related Parameter(s): P109
When active, sets the rate of acceleration for all speed increases except jog. Refer to the flowchart on
page
1-20 for details.
Values Default 20.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs
Maximum Freq
Accel Time
Accel Rate
=
Speed
0
Time
P105 [Maximum Freq]
P109 or A401
[Accel Time x]
P110 or A402
[Decel Time x]
0
Acceleration
Deceleration
A402 [Decel Time 2] Related Parameter(s): P110
When active, sets the rate of deceleration for all speed decreases except jog. Refer to the flowchart
on page
1-20 for details.
Values Default 20.0 Secs
Min/Max: 0.1/600.0 Secs
Display: 0.1 Secs
Maximum Freq
Decel Time
Decel Rate
=
Speed
0
Time
P105 [Maximum Freq]
P109 or A401
[Accel Time x]
P110 or A402
[Decel Time x]
0
Acceleration
Deceleration