Programming and Parameters 3-19
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Advanced Program Group
A401 [Accel Time 2] Related Parameter(s): P109
When active, sets the rate of acceleration for all speed increases except jog. Refer to the flowchart on
page
1-20 for details.
Values Default 20.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs
Maximum Freq
Accel Time
Accel Rate
=
Speed
0
Time
P105 [Maximum Freq]
P109 or A401
[Accel Time x]
P110 or A402
[Decel Time x]
0
Acceleration
Deceleration
A402 [Decel Time 2] Related Parameter(s): P110
When active, sets the rate of deceleration for all speed decreases except jog. Refer to the flowchart
on page
1-20 for details.
Values Default 20.0 Secs
Min/Max: 0.1/600.0 Secs
Display: 0.1 Secs
Maximum Freq
Decel Time
Decel Rate
=
Speed
0
Time
P105 [Maximum Freq]
P109 or A401
[Accel Time x]
P110 or A402
[Decel Time x]
0
Acceleration
Deceleration

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 4M and is the answer not in the manual?

Allen-Bradley PowerFlex 4M Specifications

General IconGeneral
Input Voltage200…240V AC, 380…480V AC, 500…600V AC
Output Voltage0-Input Voltage
Control MethodSensorless Vector
CommunicationsRS-485
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
EnclosureIP20
Operating Temperature-10°C to 50°C
Storage Temperature-40°C to 70°C
Humidity5-95% (non-condensing)
DimensionsVaries by model
WeightVaries by model