EasyManuals Logo

Allen-Bradley powerflex 700 User Manual

Allen-Bradley powerflex 700
198 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #81 background imageLoading...
Page #81 background image
Programming and Parameters 3-37
DYNAMIC CONTROL
Restart Modes
179 [Sleep-Wake Ref]
Selects the source of the input controlling
the Sleep-Wake function.
Default:
Options:
2
1
2
“Analog In 2”
“Analog In 1”
“Analog In 2”
180 [Wake Level]
Defines the analog input level that will
start the drive.
Default:
Min/Max:
Units:
6.000 mA, 6.000 Volts
[Sleep Level]/20.000 mA
10.000 Volts
0.001 mA
0.001 Volts
181
181 [Wake Time]
Defines the amount of time at or above
[Wake Level] before a Start is issued.
Default:
Min/Max:
Units:
1.0 Secs
0.0 Secs
0.0/30.0 Secs
0.0/1000.0 Secs
0.1 Secs
180
182 [Sleep Level]
Defines the analog input level that will
stop the drive.
Default:
Min/Max:
Units:
5.000 mA, 5.000 Volts
4.000 mA/[Wake Level]
0.000 Volts/[Wake Level]
0.001 mA
0.001 Volts
183
183 [Sleep Time]
Defines the amount of time at or below
[Sleep Level] before a Stop is issued.
Default:
Min/Max:
Units:
1.0 Secs
0.0 Secs
0.0/30.0 Secs
0.0/1000.0 Secs
0.1 Secs
182
Power Loss
177 [Gnd Warn Level]
Sets the level at which a ground warning
fault will occur. Configure with [Alarm
Config 1].
Default:
Min/Max:
Units:
3.0 Amps
1.0/5.0 Amps
0.1 Amps
259
184 [Power Loss Mode]
Sets the reaction to a loss of input power.
Power loss is recognized when:
DC bus voltage is 73% of [DC Bus
Memory] and [Power Loss Mode] is
set to “Coast”.
DC bus voltage is 82% of [DC Bus
Memory] and [Power Loss Mode] is
set to “Decel”.
Default:
Options:
0
0
1
2
3
4
“Coast”
“Coast”
“Decel”
“Continue”
“Coast Input”
“Decel Input”
013
185
185 [Power Loss Time]
Sets the time that the drive will remain in
power loss mode before a fault is issued.
Default:
Min/Max:
Units:
0.5 Secs
0.0/60.0 Secs
0.1 Secs
184
File
Group
No.
Parameter Name & Description
See page 3-2 for symbol descriptions
Values
Related
Vector
Vector
Vector
Vector
Vector v3

Table of Contents

Other manuals for Allen-Bradley powerflex 700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley powerflex 700 and is the answer not in the manual?

Allen-Bradley powerflex 700 Specifications

General IconGeneral
SeriesPowerFlex 700
CategoryAC Drive
Input Voltage200-240V AC, 380-480V AC, 500-600V AC
EnclosureType 1
Control MethodSensorless Vector
CommunicationEtherNet/IP, ControlNet, DeviceNet, PROFIBUS DP, Modbus

Related product manuals