Rockwell Automation Publication 750-PM001N-EN-P - February 2017 261
Embedded Feature and Option Module Parameters Chapter 5
File
Group
No. Display Name
Full Name
Description
Values
Read-Write
Data Type
22-Series I/O
Predictive Main
99 PredMaint Sts
Predictive Maintenance Status
RO 16-bit
Integer
Status of relay's predictive maintenance.
(1) Bit 1= “Relay Out 0” for 22-Series I/O Module models 20-750-2262C-2R and 20-750-2262D-2R
100 RO0 Load Type
Relay Output 0 Load Type
Sets the type of load that will be applied to the relay. Must be properly set for the
Predictive Maintenance function to predict the relay life.
Default:
Options:
1 = “DC Inductive
0 = “DC Resistive”
1 = “DC Inductive
2 = “AC Resistive”
3 = “AC Inductive
RW 32-bit
Integer
101 RO0 Load Amps
Relay Output 0 Load Amps
Load current that will be applied to the relay contacts. Must be properly set for the
Predictive Maintenance function to approximate the relay life.
Units:
Default:
Min/Max:
Amps
2.000
0.000 / 2.000
RW Real
102 RO0 TotalLife
Relay Output 0 Total Life
Total life cycles of the relay based on programmed load type and amps.
Units:
Default:
Min/Max:
Cycl
0
0 / 2147483647
RO 32-bit
Integer
103 RO0 ElapsedLife
Relay Output 0 Elapsed Life
Non-resettable, total accumulated cycles of the relay.
Units:
Default:
Min/Max:
Cycl
0
0 / 2147483647
RO 32-bit
Integer
104 RO0 RemainLife
Relay Output 0 Remaining Life
The difference between the Total Life and the Elapsed Life.
Units:
Default:
Min/Max:
Cycl
0
–/+2147483647
RO 32-bit
Integer
105 RO0 LifeEvntLvl
Relay Output 0 Life Event Level
Sets the percentage of relay life cycles before action is taken.
Units:
Default:
Min/Max:
%
80.000
0.000 / 100.000
RW Real
106 RO0 LifeEvntActn
Relay Output 0 Life Event Action
Sets the action that will be taken when the percentage of relay life cycles has been
reached.
“Ignore” (0) – No action is taken.
Alarm” (1) – Type 1 alarm indicated.
“Flt Minor” (2) – Minor fault indicated. If running, drive continues to run.
Enable with P950 [Minor Flt Cfg]. If not enabled, acts like a major fault.
“FltCoastStop” (3) – Major fault indicated. Coast to Stop.
“Flt RampStop” (4) – Major fault indicated. Ramp to Stop.
“Flt CL Stop” (5) – Major fault indicated. Current Limit Stop.
Default:
Options:
1 = “Alarm”
0 = “Ignore”
1 = “Alarm”
2 = “Flt Minor”
3 = “FltCoastStop”
4 = “Flt RampStop
5 = “Flt CL Stop
RW 32-bit
Integer
Options
Master
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Relay Out 0
(1)
Relay Out 0
Default0000000000000000
Bit 1514131211109876543210
0 = Condition False
1 = Condition True