86 Rockwell Automation Publication 750-PM001N-EN-P - February 2017
Chapter 3 Drive Port 0 Parameters
DRIVE CFG
Start Features
347 Auto Retry Fault
Automatic Retry Fault
RW 16-bit
Integer
Enables Retries Exhausted fault action. If the fault condition remains after the amount of time specified in P348 [Auto Rstrt Tries] elapses, an F33 “AuRsts
Exhausted” fault occurs.
348 Auto Rstrt Tries
Automatic Restart Tries
Sets the maximum number of times the drive attempts to reset a fault and restart.
Default:
Min/Max:
0 (Disabled)
0 / 9
RW 32-bit
Integer
349 Auto Rstrt Delay
Automatic Restart Delay
Sets the time between restart attempts when 348 [Auto Rstrt Tries] is set to a value
other than zero.
Units:
Default:
Min/Max:
Secs
1.00
0.50 / 30.00
RW Real
File
Group
No. Display Name
Full Name
Description
Values
Read-Write
Data Type
Options
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
AttmpsExhstd
Default0000000000000000
Bit 1514131211109876543210
0 = Condition False
1 = Condition True
ATTENTION: Equipment damage and/or personal injury may result if this parameter is used in an inappropriate
application. Do not use this function without considering applicable local, national and international codes, standards,
regulations or industry guidelines.