CIP Axis Attributes
Chapter 4
Rockwell Automation Publication MOTION-RM003I-EN-P - February 2018 377
Unwind = Conversion Constant * (Unwind Num/Unwind Denom)
Limited Travel:
Max Resolution = Int((2^31-1) * (Pos Scaling Num/Pos Scaling Denom) /
Travel Range)
Base Resolution = Minimum (Default Motion Resolution, Max
Resolution)
Motion Resolution = Pos Scaling Num * (10^(Int (Log10(Base
Resolution/Pos Scaling Num))))
Conversion Constant = Motion Resolution * (Pos Scaling Denom/Pos
Scaling Num)
Unlimited Travel:
Base Resolution = Default Motion Resolution
Motion Resolution = Pos Scaling Num * (10^(Int (Log10(Base
Resolution/Pos Scaling Num))))
Conversion Constant = Motion Resolution * (Pos Scaling Denom/Pos
Scaling Num)
When Scaling Calculations are performed, Logix Designer application sets the
Scaling Source to "from calculator". If any of the Scaling Factor attributes is
changed directly by the user either through Logix Designer or through
programmatic access, Scaling Source is set to "direct entry". The "direct entry"
setting indicates that the Scaling Factors are no longer consistent with the current
Scaling attribute values.
Travel Mode
Usage Access Data Type Default Min Max Semantics of Values
Required - All Set/ SSV# USINT 0 - - Enumeration:
0 = Unlimited
1 = Limited (E)
2 = Cyclic (E)
3-255 = reserved
# Indicates the attribute cannot be set while the tracking command (Tracking Command bit in CIP Axis Status is true).
Enumerated attribute used to determine the travel constraints of the axis.
Unlimited travel is for axes that run continuously without limit but are not cyclic.
Limited travel is for axes that have imposed limits to their travel, usually due to
mechanical limitations. Cyclic travel is for axes whose position repeats as part of a
product cycle. While the axis may run continuously, the position value is bound
between 0 and the Position Unwind value. If the Feedback Configuration = No

Table of Contents

Other manuals for Allen-Bradley PowerFlex 755

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 755 and is the answer not in the manual?

Allen-Bradley PowerFlex 755 Specifications

General IconGeneral
CategoryAC Drive
Amperage2.2…1470 A
Output Voltage0 to Input Voltage
Output Current2.2…1470 A
EnclosureIP20, IP30, IP54
CommunicationsEtherNet/IP, ControlNet, DeviceNet
I/ODigital, Analog, Encoder, Relay
SafetySafe Speed Monitor
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overload, Short Circuit, Ground Fault, Overtemperature
Operating Temperature-10°C to 50°C (14°F to 122°F)
Storage Temperature-40°C to 70°C (-40°F to 158°F)
Humidity5…95% noncondensing
AltitudeUp to 1000m (3300ft) without derating
Voltage200-240V AC, 380-480V AC, 500-600V AC, 690V AC
Input Voltage200-240V AC, 380-480V AC, 500-600V AC, 690V AC
Control MethodSensorless Vector