2-62 Digital Inputs
Figure 2.6 Typical digital input conguration with 3-wire start
Figure 2.7 represents a typical digital input configuration that includes “Run
Fwd/Rev” start. The digital input configuration parameters should be set up
as follows:
[Digital In1 Sel] = “Run Forward”.
[Digital In2 Sel] = “Run Reverse”.
[Digital In3 Sel] = “Jog Forward”.
[Digital In4 Sel] = “Jog Reverse”
[Digital In5 Sel] = “Accel 2 & Decel 2”.
[Digital In6 Sel] = “Speed Select 1”.
Figure 2.7 Typical digital input conguration with Run Fwd/Rev start
Digital In1
Digital In2
Digital In3
Digital In4
Digital In5
Digital In6
Common
Start
Stop - CF
Forward/Reverse
Jog
Speed Select 2
Enable
Digital In1
Digital In2
Digital In3
Digital In4
Digital In5
Digital In6
Common
Run Forward
Run Reverse
Jog Forward
Jog Reverse
Accel 2/Decel 2
Speed Select 1

Table of Contents