P54x/EN ST/La4 Settings
(ST) 4-66
MiCOM P543, P544, P545, P546
ST
Setting range
Menu text Default setting
Min. Max.
Step size
CB2F SC Shot 1 Disabled Enabled or Disabled
This setting determines whether a system chec e etc) is required k (e.g. live bus / dead lin
for the first shot reclosure of CB2 as follower. If Enabled, system check is required for the
first shot reclosure. If Disabled, system check is not required for the first shot reclosure.
CB2F SC CS1 Disabled Enabled or Disabled
This tting enables CB2 to auto-reclose as follower wse hen the system satisfies all the
System Check Synchronism Stage 1 conditions as listed under setting CB2 CS1 Status in
the SYSTEM CHECKS column.
CB2F SC CS2 Disabled Enabled or Disabled
This setting enables CB2 to auto-reclose as follower when system satisfies all the System
Check Synchronism St s liste S2 Sta s in the age 2 conditions a d under setting CB2 C tu
SYSTEM CHECKS settings.
CB2F SC DLLB Disabled Enabled or Disabled
This setting enables CB2 to auto-reclose as follower when the dead line & live bus 2
conditions are satisfied in the SYSTEM CHECKS column.
CB2F SC LLDB Disabled Enabled or Disabled
This setting enables CB2 to auto-reclose as follower when the live line & dead bus 2
conditions are satisfied in the SYSTEM CHECKS column.
CB2F SC DLDB Disabled Enabled or Disabled
This setting enables CB2 to auto-reclose as follower when the dead line & dead bus 2
conditions are satisfied in the SYSTEM CHECKS settings.
1.3.22 I
T at is
a icted to 16 characters and is available if ‘Input Labels’
a
nput labels
he column GROUP x INPUT LABELS is used to individually label each opto input th
vailable in the relay. The text is restr
re set visible under CONFIGURATION column.
Setting range
Menu text Default setting Step size
Min. Max.
Opto Input 1 Input L1 16 characters custom name
Label for Opto Input 1
Opto Input x Input Lx 16 characters custom name
Label for other Opto Inp . x = up to 32, depe ng on relay model. uts ndi
1.3.23 O
T that
i t
L
utput labels
he column GROUP x OUTPUT LABELS is used to individually label each output relay
s available in the relay. The text is restricted to 16 characters and is available if ‘Outpu
abels’ are set visible under CONFIGURATION column.
Setting range
Menu text Default setting Step size
Min. Max.
Relay 1 Output R1 16 characters custom name
Label for output relay 1
Relay x Output Rx 16 characters custom name
Label for other output relays. x = up to 32, depending on relay model.