1.6.13 LED conditioner properties
LED Con
ditioner
1. Select
the LED name from the list (only shown when inserting a new symbol).
2. Configure the LED output to be Red, Yellow or Green.
Configure a Green LED by driving the Green DDB input.
Configure a RED LED by driving the RED DDB input.
Configure a Yellow LED by driving the RED and GREEN DDB inputs simultaneously.
PL
3.
Configure the LED output to be latching or non-latching.
1.6.14 Contact conditioner properties
Each
contact can be conditioned with an associated timer that can be selected for pick up,
drop off, dwell, pulse, pick-up/drop-off, straight-through, or latching operation.
“Straight-through” means it is not conditioned in any way whereas “latching” is used to create
a sealed-in or lockout type function.
4. Select the contact name from the Contact Name list (only shown when inserting a new
symbol).
5. Choose the conditioner type required in the Mode tick list.
6. Set the Pick-up Time (in milliseconds), if required.
7. Set the Drop-off Time (in milliseconds), if required.