EasyManua.ls Logo

Alstom MiCOM P546 - LED conditioner properties; Contact conditioner properties

Alstom MiCOM P546
1024 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programmable Logic P54x/EN PL/La4
MiCOM P543, P544, P545 & P546
(PL) 7-13
1.6.13 LED conditioner properties
LED Con
ditioner
1. Select
the LED name from the list (only shown when inserting a new symbol).
2. Configure the LED output to be Red, Yellow or Green.
Configure a Green LED by driving the Green DDB input.
Configure a RED LED by driving the RED DDB input.
Configure a Yellow LED by driving the RED and GREEN DDB inputs simultaneously.
PL
3.
Configure the LED output to be latching or non-latching.
1.6.14 Contact conditioner properties
Each
contact can be conditioned with an associated timer that can be selected for pick up,
drop off, dwell, pulse, pick-up/drop-off, straight-through, or latching operation.
“Straight-through” means it is not conditioned in any way whereas “latching” is used to create
a sealed-in or lockout type function.
4. Select the contact name from the Contact Name list (only shown when inserting a new
symbol).
5. Choose the conditioner type required in the Mode tick list.
6. Set the Pick-up Time (in milliseconds), if required.
7. Set the Drop-off Time (in milliseconds), if required.

Table of Contents

Related product manuals