2.3.18 Switch on to fault (SOTF) and trip on reclose (TOR) (Distance option only)
2.3.19
Switch onto fault mode (Distance option only)
To en
sure fast isolation of faults (for example a closed three phase earth/grounding switch)
upon energization, it is recommended this feature is enabled with appropriate zones and/or
‘Current No Volt’ (CNV) level detectors, depend on utility practices.
When busbar VTs are used, ‘Pole Dead’ signal will not be produced and a user has to
connect circuit breaker auxiliary contacts for correct operation. This is not necessary if the
SOTF is activated by an external pulse.
SOTF delay
- The time chosen should be longer than the slowest delayed-
auto-reclose dead time, but shorter than the time in which the
system operator might re-energize a circuit once it had
opened/tripped. 110 seconds is recommended as a typical
setting.
SOTF pulse
- Typically this could be set to at 500 ms. This time is enough to
establish completely the voltage memory of distance protection.
TOC reset delay
- 500 ms is recommended as a typical setting (chosen to be in
excess of the 16 cycles length of memory polarizing, allowing
full memory charging before normal protection resumes).