EasyManua.ls Logo

Alstom MiCOM P546 - 3.2.10 Load avoidance; 3.2.11 Additional settings for quadrilateral applications; 3.2.11.1 Phase fault resistive reaches (Rph)

Alstom MiCOM P546
1024 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P54x/EN AP/La4 Application Notes
(AP) 6-58
MiCOM P543, P544, P545 & P546
AP
Remote Zone 2 reach = (Blue River-Green Valley) line impedance +
50%n (Green Valley-Tiger Bay) line
impedance
= (100+40) x 0.484 79.4 x 0.12
= 8.13 79.4 secondary
Z4 ((8.13 79.4) x 120%) - (5.81 79.4)
= 3.95 79.4
Minimum zone 4 reverse reach setting = 3.96 80 ohms secondary
3.2.10 Load avoidance
The maximu
m full load current of the line can be determined from the calculation:
I
FLC
= [(Rated MVA
FLC
) / (3 x Line kV)]
In practice, relay settings must allow for a level of overloading, typically a maximum current
of 120% IFLC prevailing on the system transmission lines. Also, for a double circuit line,
during the auto-reclose dead time of fault clearance on the adjacent circuit, twice this level of
current may flow on the healthy line for a short period of time. Therefore the circuit current
loading could be 2.4 x IFLC.
With such a heavy load flow, the system voltage may be depressed, typically with phase
voltages down to 90% of Vn nominal.
Allowing for a tolerance in the measuring circuit inputs (line CT error, VT error, relay
tolerance, and safety margin), this results in a load impedance which might be 3 times the
expected “rating”.
To avoid the load, the blinder impedance needs to be set:
Z (Rated phase-ground voltage Vn) / (IFLC x 3)
= (115/3) / (IFLC x 3)
Set the V< Blinder voltage threshold at the recommended 70% of Vn = 66.4 x 0.7 = 45 V.
3.2.11 Additional settings for quadrilateral applications
3.2.11.1
Phase fault resistive reaches (Rph)
In prima
ry impedance terms, RPh reaches must be set to cover the maximum expected
phase-to-phase fault resistance. Ideally, RPh must be set greater than the maximum fault
arc resistance for a phase-phase fault, calculated as follows:
Ra = (28710 x L)/If
1.4
Where:
If = Minimum expected phase-phase fault current (A);
L = Maximum phase conductor separation (m);
Ra = Arc resistance, calculated from the van Warrington formula ().
Typical figures for Ra (primary ) are given in the table below, for different values of
minimum expected phase fault current.
Conductor spacing
(m)
Typical system voltage
(kV)
If = 1 kA If = 2 kA If = 3 kA
4 110 - 132
7.2 2.8 1.6
8 220 - 275
14.5 5.5 3.1
11 380 - 400
19.9 7.6 4.3

Table of Contents

Related product manuals