Programmable Logic P54x/EN PL/La4
MiCOM P543, P544, P545 & P546
(PL) 7-63
PL
Relay
contact
number
P546 relay text
P546 relay
conditioner
Function
9 Output R9 Dwell 100 ms R9 CB1 Trip A
10 Output R10 Dwell 100 ms R10 CB1 Trip B
11 Output R11 Dwell 100 ms R11 CB1 Trip C
12 Output R12 Dwell 100 ms R12 CB2 Fail1Trip
13 Output R13 Dwell 100 ms R13 CntlCB2Close
14 Output R14 Dwell 100 ms R14 Cntl CB2Trip
15 Output R15 Dwell 100 ms R15 CB1 Fail2Trip
16 Output R16 Dwell 100 ms R16 CB2 Fail2Trip
17 Output R17 Dwell 100 ms R17 CB2 Trip A
18 Output R18 Dwell 100 ms R18 CB2 Trip B
19 Output R19 Dwell 100 ms R19 CB2 Trip C
20 Output R20 Dwell 100 ms R20 DistInst Trp
Note: A fault record can be generated by connecting one or a number of
contacts to the “Fault Record Trigger” in PSL. It is recommended that
the triggering contact be ‘self reset’ and not a latching. If a latching
contact were chosen the fault record would not be generated until the
contact had fully reset.
1.12 Programmable LED output mappings
The d
efault mappings for each of the programmable LEDs are as shown in the following
table:
LED
number
LED Input connection/text Latched P543 LED function indication
1 LED 1 Red Yes Diff Trip
2 LED 2 Red Yes Dist Inst Trip
3 LED 3 Red Yes Dist Delay Trip
4 LED 4 Red No Signaling Fail
5 LED 5 Red No Any Start
6 LED 6 Red No AR in Progress
7 LED 7 Red No AR Lockout
8 LED 8 Red No Test Loopback
9 FnKey LED1 Red No Not Mapped
10 FnKey LED2 Red No Not Mapped
11 FnKey LED3 Red No Not Mapped
12 FnKey LED4 Red No Not Mapped
13 FnKey LED5 Red No Not Mapped
14 FnKey LED6 Red No Not Mapped
15 FnKey LED7 Red No Not Mapped
16 FnKey LED8 Red No Not Mapped
17 FnKey LED9 Red No Not Mapped
18 FnKey LED10 Red No Not Mapped