EasyManua.ls Logo

Alstom MiCOM P546 - 1.24.1 Zone 1 extension scheme (Distance option only)

Alstom MiCOM P546
1024 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation P54x/EN OP/La4
MiCOM P543, P544, P545 & P546
(OP) 5-75
OP
1.24.1 Zone 1 extension scheme (Distance option only)
Auto-reclosure is widely used on radial overhead line circuits to re-establish supply following
a transient fault. A Zone 1 extension scheme may therefore be applied to a radial overhead
feeder to provide high speed protection for transient faults along the whole of the protected
line. Figure 50 shows the alternative reach selectio
ns for zone 1: Z1 or the extended reach
Z1X.
P1308ENa
B
A
ZL
Z1 Extension (B)
Z1 Extension (A)
Z1A
Figure 50 Zone 1 extension scheme
In this scheme, Zone 1X is enabled and set to overreach the protected line. A fault on the
line, including one in the end 20% not covered by zone 1, will now result in instantaneous
tripping followed by auto-reclosure. Zone 1X has resistive reaches and residual
compensation similar to Zone 1. The auto-recloser in the relay is used to inhibit tripping from
zone 1X such that upon reclosure the relay will operate with Basic scheme logic only, to co-
ordinate with downstream protection for permanent faults. Therefore, transient faults on the
line will be cleared instantaneously, which will reduce the probability of a transient fault
becoming permanent. The scheme can, however, operate for some faults on an adjacent
line, although this will be followed by auto-reclosure with correct protection discrimination.
Increased circuit breaker operations would occur, together with transient loss of supply to a
substation.
The time delays associated with extended zone Z1X are shown in the table below:
Scenario Z1X time delay
First fault trip = tZ1
Fault trip for persistent fault on auto-reclose = tZ2
The Zone 1X reach is set as a percentage of the Zone 1 reach, i.e. as a reach multiplier.
The Zone 1 extension scheme can be Disabled, permanently Enabled or just brought into
service when the distance communication channel fails and the aided scheme would be
inoperative. A selection of which out of the two channels available in the MiCOM P54x is
monitored, is provided, with selections from Channel 1 and Channel 2 in any combination.
The Logic Diagram is shown in Figure 51 below:

Table of Contents

Related product manuals