EasyManua.ls Logo

Alstom MiCOM P546 - Page 230

Alstom MiCOM P546
1024 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P54x/EN OP/La4 Operation
(OP) 5-56
MiCOM P543, P544, P545 & P546
OP
P1239ENa
P1134ENa
Z
L1
Z
R1
Z
S1
Z
L2
Z
R2
Z
S2
Z
L0
Z
R0
Z
S0
I
F1
I
F2
I
F0
I
1
I
2
I
0
V
1
V
2
V
0
I
F/3
E
voltage
generator
represents
voltage
change
at fault
location
Figure 31 Sequence networks connection for an internal A-N fault
(Distance option only)
The fault is shown near to the busbar at end R of the line, and results in a connection of the
positive, negative, and zero sequence networks in series. Drawing the delta diagram, it is
seen that any fault is effectively a generator of , connected at the location of fault inception.
The characteristics are:
1. The I generated by the fault is equal to the total fault arc current;
2. The I will split into parallel paths, with part contribution from source “S”, and part from
remote end “R” of the line. Therefore, each relay will measure a lower proportion of
delta I;
3. The V generated by the fault is equal to the fault arc voltage minus the prefault
voltage (and so will be in antiphase with the prefault voltage);
4. The V will generally be smaller as measured at the relay location, due to the voltage
collapse being smaller near to the source than at the fault itself. The delta V
measured by a relay is effectively the voltage drop across the source impedance
behind the relay location.
If a fault were to occur at any point on the protected line, the resulting I and V as
measured at the relay location must be greater than the Delta I Fwd and Delta V Fwd
settings, in order that the fault can be detected. (Scenarios (2) and (4) above must be
verified for all fault types: Ph-G, Ph-Ph, Ph-Ph-G, and 3-phase)

Table of Contents

Related product manuals