P54x/EN TD/La4 Technical Data
(TD) 2-2
MiCOM P543, P544, P545 & P546
TD
Ratings
AC measuring inputs
Nominal frequency: 50 and 60 Hz (settable)
Operating range: 45 to 65 Hz
Phase rotation: ABC or CBA
AC current
Nominal current (In): 1 and 5 A dual rated.
(1 A and 5 A inputs use different transformer
tap connections, check correct terminals are
wired).
Nominal burden per phase: < 0.15 VA at In
Thermal withstand:
continuous 4 In
for 10 s: 30 In
for 1 s; 100 In
Linear to 64 In (non-offset AC current).
AC voltage
Nominal voltage (Vn): 100 to 120 V phase-
phase.
Nominal burden per phase: < 0.02 VA at Vn.
Thermal withstand:
continuous 2 Vn
for 10 s: 2.6 Vn
Power supply
Auxiliary voltage (Vx)
Three ordering options:
(i) Vx: 24 to 48 Vdc
(ii) Vx: 48 to 110 Vdc, and 40 to
100 Vac (rms)
(iii) Vx: 110 to 250 Vdc, and 100 to
240 Vac (rms)
Operating range
(i) 19 to 65 V (dc only for this variant)
(ii) 37 to 150 V (dc), 32 to 110 V (ac)
(iii) 87 to 300 V (dc), 80 to 265 V (ac)
With a tolerable ac ripple of up to 12% for a dc
supply, per IEC 60255-11: 1979.
Nominal burden
Quiescent burden: 11W. (Extra 1.25 W when
fitted with second rear communications board)
Additions for energized binary inputs/outputs:
Per opto input:
0.09 W (24 to 54 V),
0.12 W (110/125 V),
0.19 W (220/120 V).
Per energized output relay: 0.13 W
Power-up time
Time to power up < 11 s.
Power supply interruption
Per IEC 60255-11: 1979
The relay will withstand a 20 ms interruption
in the DC auxiliary supply, without
de-energizing.
Per IEC 61000-4-11: 1994
The relay will withstand a 20 ms interruption
in an AC auxiliary supply, without
de-energizing.
Battery backup
Front panel mounted
Type ½ AA, 3.6 V Lithium Thionyl Chloride
Battery
Field voltage output
Regulated 48 Vdc
Current limited at 112 mA maximum output
Digital (“Opto”) inputs
Universal opto inputs with programmable
voltage thresholds. May be energized from the
48V field voltage, or the external battery
supply.
Rated nominal voltage: 24 to 250 Vdc
Operating range: 19 to 265 Vdc
Withstand: 300 Vdc.
Nominal pick-up and reset thresholds:
Nominal Battery 24/27: 60 - 80% DO/PU
(logic 0) <16.2 (logic 1) >19.2
Nominal Battery 24/27: 50 - 70% DO/PU
(logic 0) <12.0 (logic 1) >16.8
Nominal Battery 30/34: 60 - 80% DO/PU
(logic 0) <20.4 (logic 1) >24.0
Nominal Battery 30/34: 50 - 70% DO/PU
(logic 0) <15.0 (logic 1) >21.0
Nominal Battery 48/54: 60 - 80% DO/PU
(logic 0) <32.4 (logic 1) >38.4
Nominal Battery 48/54: 50 - 70% DO/PU
(logic 0) <24.0 (logic 1) >33.6
Nominal Battery 110/125: 60 - 80% DO/PU
(logic 0) <75.0 (logic 1) >88.0
Nominal Battery 110/125: 50 - 70% DO/PU
(logic 0) <55.0 (logic 1) >77.0
Nominal Battery 220/250: 60 - 80% DO/PU
(logic 0) <150.0 (logic 1) >176.0
Nominal Battery 220/250: 50 - 70% DO/PU
(logic 0) <110 (logic 1) >154
Recognition time:
<2 ms with long filter removed,
<12 ms with half-cycle ac immunity
filter on.