P54x/EN OP/B94 Operation
(OP) 5-250
MiCOM P543, P544, P545, P546
OP
&
1
&
&
&
&
DDB: CB2 Man SCOK(1458)
DDB: Dead Line(889)
DDB: Dead Line(889)
DDB: Dead Bus2(1462)
DDB: Dead Bus2(1462)
DDB:CB2 CS1 OK(1577)
DDB:CB2 CS2 OK(1463)
DDB: Live Bus2(1461)
DDB: Live Line(888)
Setting:
CB2M SC CS1:
Enabled/Disabled
Enabled
Setting:
CB2M SC CS2
Enabled/Disabled
Enabled
Setting:
CB2M SC DLLB:
Enabled/Disabled
Enabled
Setting:
CB2M SC LLDB:
Enabled/Disabled
Enabled
Setting:
CB2M SC DLDB:
Enabled/Disabled
Enabled
Setting:
CB2M SC Required:
Enabled/Disabled
Disabled
Fig 52
Fig 44
DDB: CB2 Ext CS OK(901)*
&
*Note
If not mapped in PSL
are defaulted high.
Figure 52 CB2 man. close system check