Operation P54x/EN OP/B94
MiCOM P543, P544, P545, P546
(OP) 5-265
OP
Name Description
CB2 3PDTCOMP Int Sig: CB2 3PAR dead time complete
CB2 3PFTCOMP Int Sig: CB2 3PAR follower time complete
CB2 3POK Int Sig: CB2 OK for 3P AR (leader or
follower)
CB2 ARSUCC Int Sig: CB2 auto-reclose sucessful
CB2 CS1 AngHigh- Int Sig + DDB: Line/Bus2 phase angle in
range:
-CB2 CS1 Angle to -180deg
CB2 CS1 AngHigh+ Int Sig + DDB: Line/Bus2 phase angle in
range:
+CB2 CS1 Angle to +180deg
CB2 CS1 FL<FB Int Sig + DDB: Bus2 F > (Line F + “CB2
CS1 SlipFreqf”)
CB2 CS1 FL>FB Int Sig + DDB: Line F > (Bus2 F + “CB2
CS1 SlipFreqf”)
CB2 CS1 OK Int Sig + DDB: CB2 CS1 is enabled and
Line and Bus 2 voltages meet CB2 CS1
settings
CB2 CS1 SlipF< Int Sig + DDB: Line-Bus 2 slip freq < CB2
CS1 SlipFreq setting
CB2 CS1 SlipF> Int Sig + DDB: Line-Bus 2 slip freq > CB2
CS1 SlipFreq setting
CB2 CS1 VL<VB Int Sig + DDB: Bus2 V > (Line V + “CB2
CS1 VDiff”)
CB2 CS1 VL>VB Int Sig + DDB: Line V > (Bus2 V + “CB2
CS1 VDiff”)
CB2 CS2AngHigh- Int Sig + DDB: Line/Bus2 phase angle in
range:
-CB2 CS2 Angle to -180deg
CB2 CS2AngHigh+ Int Sig + DDB: Line/Bus2 phase angle in
range:
+CB2 CS2 Angle to +180deg
CB2 CS2FL<FB Int Sig + DDB: Bus2 F > (Line F + “CB2
CS2 SlipFreqf”)
CB2 CS2FL>FB Int Sig + DDB: Line F > (Bus2 F + “CB2
CS2 SlipFreqf”)
CB2 CS2OK Int Sig + DDB: CB2 CS2 is enabled and
Line and Bus 2 voltages meet CB2 CS2
settings
CB2 CS2SlipF< Int Sig + DDB: Line-Bus 2 slip freq < CB2
CS2 SlipFreq setting
CB2 CS2SlipF> Int Sig + DDB: Line-Bus 2 slip freq > CB2
CS2 SlipFreq setting
CB2 CS2VL<VB Int Sig + DDB: Bus2 V > (Line V + “CB2
CS2 VDiff”)
CB2 CS2VL>VB Int Sig + DDB: Line V > (Bus2 V + “CB2
CS2 VDiff”)
CB2 FARIP Int Sig: CB2 ARIP as follower