EasyManua.ls Logo

Alstom MiCOM P546 - Page 567

Alstom MiCOM P546
1024 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programmable Logic P54x/EN PL/La4
MiCOM P543, P544, P545 & P546
(PL) 7-33
PL
DDB no. English text Source Description
844 AR 3pole in prog (CB1) Auto-Reclose
Auto-reclose 3 pole in progress (dead time is
running)
845 AR 1pole in prog (CB1) Auto-Reclose
Single pole auto-reclose in progress (dead
time is running)
846 Seq Counter = 0 Auto-Reclose
Auto-reclose sequence counter is at zero - no
previous faults have been cleared within
recent history. The sequence count is at zero
because no reclaim times are timing out, and
the auto-recloser is not locked out. The
recloser is awaiting the first protection trip, and
all programmed cycles are free to follow
847 Seq Counter = 1 Auto-Reclose
The first fault trip has happened in a new
auto-reclose sequence. Dead time 1, or
reclaim time 1 are in the process of timing out
848 Seq Counter = 2 Auto-Reclose
Auto-reclose sequence counter is at 2. This
means that the initial fault trip happened, and
then another trip followed, moving the counter
on to 2
849 Seq Counter = 3 Auto-Reclose
Auto-reclose sequence counter is at 3. This
means that the initial fault trip happened, and
then 2 trips followed, moving the counter on to
3
850 Seq Counter = 4 Auto-Reclose
Auto-reclose sequence counter is at 4. This
means that the initial fault trip happened, and
then 3 trips followed, moving the counter on to
4
851 Reserved
852 Successful Close (CB1) Auto-Reclose
Successful re-closure indication. The circuit
breaker was re-closed by the AR function, and
stayed closed. This indication is raised at the
expiry of the reclaim time
853 3P Dead Time IP Auto-Reclose
3 pole Auto-reclose dead time in progress
P544 and P546 only
854 Auto Close (CB1) Auto-Reclose Auto-reclose command to the circuit breaker
855 CB2 AR 1p InProg Auto-reclose CB2
Single pole auto-reclose in progress (dead
time is running) CB2
P544 and P546 only
856 A/R Status 3P Auto-Reclose
3 Pole auto-recloser in service - the auto-
reclose function has been enabled either in the
relay menu, or by an opto input
P544 and P546 only
857 AR Status 1P Auto-Reclose
Single pole auto-recloser in service - the
auto-reclose function has been enabled either
in the relay menu, or by an opto input
P544 and P546 only
858 Force 3 pole (CB1) Auto-Reclose
Due to the sequence count reached, lockout,
or any outage of the internal auto-recloser -
this signal instructs any other trips to be forced
to three pole trips
859 AR Blocked Auto-Reclose
It indicates that AR has been blocked (ex. from
external input BAR)
860 Lockout Alarm (CB1) CB Control
Composite lockout alarm - circuit breaker
locked out due to auto-recloser, or condition
monitoring reasons
861 GPSAlarm Instant C Diff
Instantaneous GPS Alarm initiated
immediately on loss of the GPS 1 pulse per
second input signal
862 to 863 Not used

Table of Contents