Programmable Logic P54x/EN PL/La4
MiCOM P543, P544, P545 & P546
(PL) 7-53
PL
DDB no. English text Source Description
1589 CB1 CS2 VL<VB
Bus1 V > (Line V + [VDiff1-2])
P544 and P546 only
1590 CB1 CS1 FL>FB
Line F > (Bus1 F + [SlipFr1-1])
P544 and P546 only
1591 CB1 CS1 FL<FB
Bus1 F > (Line F + [SlipFr1-1])
P544 and P546 only
1592 CB1 CS1 AngHigh+
Line/Bus1 phase angle in range: +Angle 1-1 to
+180deg
P544 and P546 only
1593 CB1 CS1 AngHigh-
Line/Bus1 phase angle in range: -Angle 1-1 to
-180deg
P544 and P546 only
1594 CB1 CS AngRotACW
Line freq > (Bus1 freq + 0.001Hz) (CS1 Angle
Rotating Anticlockwise)
P544 and P546 only
1595 CB1 CS AngRotCW
Bus1 freq > (Line freq + 0.001Hz) (CS1 Angle
Rotating Clockwise)
P544 and P546 only
1596 Not used
1597 Rst CB2 Data
Rst CB2 All Val
P544 and P546 only
1598 CB2 Pre-Lockout
Output from CB2 monitoring logic
1599 CB2 LO Alarm
CB2 LO Alarm
P544 and P546 only
1600 CB2 Trip 3ph Trip Conversion Logic
3 Phase Trip 2
P544 and P546 only
1601 CB2 Trip OutputA Trip Conversion Logic
A Phase Trip 2
P544 and P546 only
1602 CB2 Trip OutputB Trip Conversion Logic
B Phase Trip 2
P544 and P546 only
1603 CB2 Trip OutputC Trip Conversion Logic
C Phase Trip 2
P544 and P546 only
1604 Force 3PTrip CB2 PSL
External input via DDB to force host relay trip
conversion logic to issue a three phase trip
signal to CB2 for all faults
P544 and P546 only
1605 Enable AR CB2
External input via DDB to enable CB2, if "in
service", to be initiated for autoreclosing by an
AR initiation signal from protection. DDB input
defaults to high if not mapped in PSL, so CB2
AR initiation is permitted.
P544 and P546 only
1606 Pole Discrep.CB2 PSL
Pole Discrepancy
P544 and P546 only
1607 Pole Discrep.CB2 Pole discrepency
Pole Discrepancy
P544 and P546 only
1608 CB2 Trip I/P 3Ph PSL
Trip 3 Phase - Input to Trip Latching Logic
P544 and P546 only