Quick Start Guide
5
1.6 Mounting The Electronic Unit
• Theintegralelectronicunitismountedwiththesensing
element
• Theremoteelectronicunitisdesignedforfield
mounting, but should be mounted in a location free from
vibration, corrosives, and any mechanical damage
• Ratedtemperaturesformounting:mounttheUIV
CM in a reasonably accessible location with ambient
temperaturesbetween-40°Fand167°F(-40°Cand75°C)
• Wheninstallingconduittoelectronicunit,besurethat
vertical conduit runs will not cause water to enter the
electronic unit housing as show below
Figure 1-2
Recommended Conduit Installation