EasyManuals Logo

Ansul AUTOPULSE IQ-301 User Manual

Ansul AUTOPULSE IQ-301
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #184 background imageLoading...
Page #184 background image
Expansion Power Supplies Installation
184 IQ-301 PN 50036:F 10/29/2001
.
Table 69 APS-6R Wiring Instructions
Step Action
1 Connect AC power:
2 Connect the battery:
3 Connect the Power Harness to control panel NACs 3 and 4 as follows:
Cut jumpers JP6 and JP7 on the CPU board (Figure 166).
Plug the Power Harness (PN 71093) into plug J10 on the CPU board (Figure 166) as
follows:
Connect J10 (–) to TB2 terminal 2 on the APS-6R.
Connect J10 (+) to TB2 terminal 1 on the APS-6R.
4 Connect the Supervisory cable to the control panel as follows:
Cut jumper JP3 on the CPU board (Figure 166)
Plug the gray Supervisory Cable (PN 71033) into J11 on the CPU board (Figure
166) with the wires exiting the connector on top.
Plug the other end of the Supervisory Cable into J3 on the APS-6R (Figure 166).
Wire and Color from APS-6R... to Control Panel...
Earth Ground (green) TB1 terminal 3 TB7 terminal 3
AC Hot (black) TB1 terminal 1 TB7 terminal 1
AC Neutral (white) TB1 terminal 2 TB7 terminal 2
Wire and Color from APS-6R... to Control Panel...
Battery – (black) TB3 terminal 2 connector J3 (–)
Battery + (red) TB3 terminal 1 connector J3 (+)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ansul AUTOPULSE IQ-301 and is the answer not in the manual?

Ansul AUTOPULSE IQ-301 Specifications

General IconGeneral
BrandAnsul
ModelAUTOPULSE IQ-301
CategoryFire Alarms
LanguageEnglish

Related product manuals