Technical Documentation ECE10CM, DC10CM Page 11 of 39
3. Technical Data
3.1 General Data / Operating Conditions
Temperature range: 0°C ... +40°C without power-loss
40°C ... +70°C with power-loss
Altitude tolerance: under 1000m without power-loss
over 1000m with power-loss
Humidity tolerance: Humidity class F without condensation
(average relative humidity 85%)
Degree of soiling: VDE 0110 Part 2 level 2
Interference emission: EN 50081-2, EN 50082-1 requirements
Class B limits per EN 55011 (residential)
Interference immunity: Meets standards without mains filter.
Requirements per EN 50082-2
Requirement Norm Intensity
Burst EN 61000-4-4 4kV
ESD EN 61000-4-2 Enclosure 8KV
Connectors 4kV
Voltage drops EN 61000-4-11
High frequency EN 50141 10V/m
Voltage surge EN 61000-4-5 Class 1
Insulation: Over-voltage category II per VDE 0100
Protection class: IP 00
Mounting position: vertical
100
80
60
40
20
40 60
50 70
Output
Power
in %
Temperature in °C
100
80
60
40
20
1000
2000
3000
4000
5000
Output
Power
in %
Altitude in m