A1 35 DTR.APC.APR.ALW.03
(ENG)
% SQRT______ (Square root characteristic cut-of point setting)
| \
|
BACK (Return to Local Menu. If you will confirm this option,
| | you will come back to main tree of Local Menu)
| |
| | (Confirm one of the following percent value across
| | longer press button . After parameter confirmation
| | transmitter will confirm the party of command by the "DONE")
| |
| 0.0 %
| 0.2 %
| 0.4 %
| 0.6 %
| 0.8 %
| 1.0 %
LCD1 VAR
iable
__ (Type of the process variable displayed on LCD1)
| \
|
BACK (Return to Local Menu. If you will confirm this option,
| | you will come back to main tree of Local Menu)
| |
| | (Confirm one of the following option across
| | longer press button . After parameter confirmation
| | transmitter will confirm the party of command by the "DONE")
| |
| CURRENT (On LCD1 will displayed current value in current loop)
| |
| |
| PERCENT (The percent value output signal will displayed on LCD1)
|
|
|
LCD2 VAR
iable
(Type of the process variable displayed on LCD2)
| \
|
BACK (Return to Local Menu. If you will confirm this option,
| | you will come back to main tree of Local Menu)
| |
| | (Confirm one of the following option across
| | longer press button . After parameter confirmation
| | transmitter will confirm the party of command by the "DONE")
| |
| |
| PRESSURe (The pressure value will displayed on LCD2)
| |
| USER (The user’s units will displayed on LCD2)
| |
| |
| UNIT* (The current unit or user’s unit alternately
| | with process variable will displayed on LCD2)
| SENS_T* (The current temperature of pressure sensor will displayed on LCD2)
| |
| |
| NO UNIT* (The current unit or user’s unit alternately
| with process variable will not displayed on LCD2)
| CPU_T* (The current temperature of the transmitter CPU will displayed on
LCD2)
*) for older versions of transmitters are displayed a UNIT and NO UNIT sequences , in solutions since 2011:
are SENS_T and CPU_T sequences