22
20
Backlight control
Backlight on (default)
Backlight off
22
Beeps while primary source
is interrupted
Alarm on (default)
Alarm off
23
Overload bypass:
When enabled, the unit will
transfer to line mode if
overload occurs in battery
mode.
Bypass disable (default)
Bypass enable
25
Record Fault code
Record enable (default)
Record disable
26
Bulk charging voltage
(C.V voltage)
56.4V (default)
If user-defined is selected in
program 5, this program can
be set up. Setting range is
from 48.0V to 62.0V.
Increment of each click is
0.1V.
27
Floating charging voltage
54V (default)
If user-defined is selected in
program 5, this program can
be set up. Setting range is
from 48.0V to 62.0V.
Increment of each click is
0.1V.
28
AC output mode
*This setting is only
available when the inverter
is in standby mode (Switch
off).
Single: This inverter is used in
single phase application.
Parallel: This inverter is
operated in parallel system.