2.6 Hand Held Unit
The Hand Held Unit, when connected to the Remote connector on the PMC Front Panel, has
controls, which duplicate controls on the PMC Front Panel. The Hand Held Unit has a 4 digit
display, lighted pushbuttons and a MODIFY UP/DOWN Rocker Switch which duplicate the
function of the numeric portion of the PMC display, the keys and LED indicators, and the
MODIFY UP/DOWN keys, respectively.
In addition to displaying numeric values, the Hand Held Unit display uses error codes, as shown in
Table 2.3, to indicate errors that are displayed in message form on the PMC display. The Hand
Held Unit keys can be used interchangeably with the corresponding PMC front panel keys.
Once an output function is set up on the PMC, the Hand Held Unit may be used to alter the output;
i.e. MODIFY, DEV (%), NORMAL, OPERATE or STBY. The Hand Held Unit also has
pushbuttons for the STORE and RECALL functions.
2.7 GPIB Operation
2.7.1 General
The PMC has a fully functional GPIB port that provides for remote or automatic operation with a
GPIB instrument controller. All functions of the PMC, except MODIFY, may be operated
through GPIB commands. The PMC has the following IEEE-488 capabilities:
SH1- Source Handshake; complete capability
AH1- Acceptor Handshake; complete capability
T6- Talker; Basic Taker, Serial Poll, Unaddress if MLA
L4- Listener; Basic Listener, Unaddress if MTA
SR1- Service Request; complete capability
RL2- No Local Lockout
(Front Panel Disabled, RESET Key active)
PP0- Parallel Poll; no capability
DC1- Device Clear; complete capability
DT0- Device Trigger; no capability
C0- Controller; no capability
E2- Tri State (1MB/Sec max)

Table of Contents