Air-to-water Heat Pump
19
Air removal of the water system: this function is intended to replenish water and remove air in the water system to
make the equipment run at the stabilized water pressure.
Solar water heater: when the condition for starting the solar water heater is satisfied, the solar heater will start to heat
the circulation water. Then the heated water will go to the water tank and exchange heat with water in it. At any condition,
the solar water heater will be given priority for startup so as for energy conservation.
Other thermal: when the outdoor temperature is lower than the set point for starting other thermal and the unit is under
the error condition and the compressor has stopped for three minutes, the other thermal will start to supply heat or hot
water to the room.
Model Line-Up
Model
Heating
1
Power supply
Capacity, kW
Power Input, kW
COP, W/W
AG4HP061PH
6.0
1.111
5.40
230 VAC,
1-ph, 50 Hz
AG4HP081PH
8.2
1.54
5.32
AG4HP101PH
10.2
2.02
5.05
AG4HP121PH
12.0
2.43
4.94
AG4HP141PH
14.2
2.99
4.75
AG4HP161PH
15.7
3.45
4.55
AG4HP103PH
10.2
2.06
4.95
400 VAC,
3-ph, 50 Hz
AG4HP123PH
12.0
2.49
4.82
AG4HP143PH
14.2
3.09
4.60
AG4HP163PH
15.7
3.57
4.40
Model
Cooling
2
Power supply
Capacity, kW
Power Input, kW
EER, W/W
AG4HP061PH
6.5
1.275
5.10
230 VAC,
1-ph, 50 Hz
AG4HP081PH
8.3
1.56
5.32
AG4HP101PH
10.2
2.00
5.10
AG4HP121PH
12.0
2.45
4.90
AG4HP141PH
13.7
3.00
4.57
AG4HP161PH
15.5
3.60
4.31
AG4HP103PH
10.2
2.13
4.79
400 VAC,
3-ph, 50 Hz
AG4HP123PH
12.0
2.61
4.60
AG4HP143PH
13.9
3.32
4.19
AG4HP163PH
15.4
4.05
3.80
Notes
(a)
1
Capacities and power inputs are based on the following conditions: Indoor Water Temperature 30°C/35°C,
Outdoor Air Temperature 7°C DB/6°C WB;
(b)
2
Capacities and power inputs are based on the following conditions: Indoor Water Temperature 23°C/18°C,
Outdoor Air Temperature 35°C DB/24°C WB.
(c) In caso di installazione di resistenze ausiliarie, il dimensionamento dei cavi deve essere calcolato da un tecnico
qualificato.
Operating conditions:
Mode
Heat Source Side Temperature (°C)
User Side Temperature (°C)
Heating
- 25~35
20~65
Cooling
-15~48
5~25
Water Heating
- 25~45
40~55/80