Air-to-water Heat Pump
37
The minimum clearance from the water tank to combustible surface must be 500mm.
There should be water pipe, hot water joint and floor drain near the water tank in favor of water replenishment, hot water
supply and drainage of water tank.
Connection of inlet/outlet waterway: Connect the safety check valve attached with the unit (with the arrow on it pointing
at the water tank) with the water inlet of water tank with PPR pipe according to the following figure, sealing with unsintered
tape. The other end of the safety check valve should connect with tap water joint. Connect the hot water pipe and water
outlet of water tank with PPR pipe.
Notes.
(1) For safe use of water, water outlet/inlet of water tank must connect with a certain length of PPR pipe ,L ≥70×R2(cm,
R is inside radius of the pipe). Moreover, heat preservation should be conducted and metal pipe cannot be used.
For the first use, water tank must be full of water before the power is on.
(2) The water may drip from the discharge pipe of the pressure-relief device and that this pipe must be left open to the
atmosphere.
(3) The pressure-relief device is to be operated regularly to remove lime deposits and to verify that it is not blocked.
(4) The discharge pipe connected to the pressure-relief device is to be installed in a continuously downward direction
and in a frost-free environment.
(5) The appliance is intended to be permanently connected to the water mains and not connected by a hoseset.
(6) The type of the pressure-relief device is A3J, and this device shall be installed with threaded connection.
(7) The replenishing water pressure in water tank shall be beyond 0.2MPa and below 0.7MPa.
(8) The method of water drainage must be operated strictly abide by the instruction on the label of the water
tank
Tank
Safety valve
Tap water
Secure
with
bolts
Install on the ground
(not hanged)