4. GAS ADJUSTMENTS
CATEGORY II2H3+ Methane Gas
G
20
Liquid Butane Gas
G
31
Liquid Propane Gas
G
30
L
ower Wobbe Index (15°C;1013mbar) MJ/m
3
h
Nominal Delivery Pressure mbar
M
inimum Delivery Pressure mbar
4
5.67
20
2
0
8
0.58
29
2
8
8
0.58
37
3
6
0.70
-
--
2.86 - 0.85
35.6 - 6.8
0.78
---
2.17 - 0.93
36.0 - 7.1
0.78
---
2.45 - 0.93
36.0 - 7.0
0.70
---
1
.89 - 0.87
2
9.0 - 5.5
0.74
---
2.21 - 0.95
27.5 - 5.4
0.74
---
2.48 - 0.95
28.0 - 5.4
1.30
2.54 - 1.16
-
--
7
.5 - 1.7
1.30
2.96 - 1.27
---
9.5 - 1.8
1.30
3.33 - 1.27
---
12.0 - 1.8
microGENUS HE 24 MFFI
Main Burner: n. 14 jets (ø) mm
Consumption (15°C; 1013mbar) max - min m
3
/h
C
onsumption (15°C; 1013mbar) max - min Kg/h
Gas Burner Pressure
m
ax - min mbar
microGENUS HE 28 MFFI
Main Burner: n. 14 jets (ø) mm
Consumption (15°C; 1013mbar) max - min m
3
/h
Consumption (15°C; 1013mbar) max - min Kg/h
Gas Burner Pressure
max - min mbar
microGENUS HE 32 MFFI
Main Burner: n. 14 jets (ø) mm
Consumption (15°C; 1013mbar) max - min m
3
/h
Consumption (15°C; 1013mbar) max - min Kg/h
Gas Burner Pressure
max - min mbar
The boiler can be converted to use either methane
(natural) gas (G20) or L.P.G. (G30 - G31) by a CORGI
registered Gas Engineer.
The operations that must be performed are the following:
1.
Replace the jets on the main b
urner
(see
T
able A)
;
2. Adjust the maximum and minimum thermal capacity
v
alues f
or the boiler
(Section 4.2 Adjusting the Gas
Pressures);
3.
Adjust the maxim
um thermal power setting (
P
a
ge 39
and T
ABLE B
40)
;
4.
Adjust the soft-light feature
(see
Table opposite for
recommended pressure and Fig. 4.1 see page 39);
5. Adjust the ignition delay feature for the heating system
b
y adjusting the dip s
witch as indicated in Section 2.17
(FIG. 2.34). It can be turned on or off.
4.1 CHANGING THE TYPE OF GAS
CATEGORY
II2H3+
Methane
Gas
G20
Liquid
Butane
Gas
G31
Liquid
Propane
Gas
G30
Soft-light
Pressure (mbar)
24 kW Model
28 kW Model
32 kW Model
5.0
5.5
5.5
12.0
12.0
12.0
12.0
12.0
12.0
TABLE A
SOFT LIGHT PRESSURES

Table of Contents

Other manuals for Ariston microGENUS HE 28 MFFI

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ariston microGENUS HE 28 MFFI and is the answer not in the manual?

Ariston microGENUS HE 28 MFFI Specifications

General IconGeneral
BrandAriston
ModelmicroGENUS HE 28 MFFI
CategoryBoiler
LanguageEnglish

Related product manuals