It is recommended that the following inspections be
c
arried out on the boiler at least once a year:
1
.
V
isually check the appliance for correct installation;
2. Check the appliance for the correct operation;
3
.
C
heck the flue and flue installation for correct siting,
i
nstallation and that it is in good condition.;
4. Remove the casing as described in Section 7.2;
5. Check the operation of the safety devices:
- Air Pressure Switch;
- Overheat Thermostat;
- Safety Valve;
- Pump Pressure Switch;
- Ionisation (Flame Detection);
6. Drain the boiler and check the pressure in the
expansion vessel, ensuring it is 0.7 bar;
7. Remove the diverter valve motor and clean the
actuators, replacing any damaged seals as
necessary (see Exploded View on Pages 63 & 64
for more details);
8. Remove, clean and refill the condensate trap and
condensate hoses (see Section 6.3.10), check the
drain system for correct discharge of condensate
and clean if necessary;
9. Remove and clean the DHW flow switch;
10. Remove and clean the fan;
11. Remove and clean the electrodes with an emery
cloth;
12. Remove and clean the burner;
13. Check and clean the primary heat exchanger as
necessary;
14. Refill the boiler and check the following;
15. Check gas inlet pressure and correct working
pressure;
17. Check the gas rate;
18. Check the correct operations of the timeclock and
room thermostat;
19. Check the DHW flow rates;
20. Advise the customer on the correct use of the
appliance (cloc
k setting and oper
ation, repressur
ising
etc.);
21. Complete the Ser
vice Inter
v
al
Record (Section 12,
page 69).