EasyManua.ls Logo

Arkel ADrive VVVF - 13.3.6. Process of Evacuation Travel

Arkel ADrive VVVF
166 pages
Go to English
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ARKEL 127 ADrive
ENGLISH
TÜRKÇE
13.3.6. Process of an evacuation travel:
The elevator controller must be capable of performing an evacuation operation in case of a power
failure. The following operations must be carried out respectively by the elevator control system:
Control detects mains failure.
Control recognizes inverter fault.
Control waits a certain time for the mains power to restore or for a generator to go online.
Control disconnects the mains supply from inverter by releasing the KSAK contactor.
Control activates the KKAK contactor after a certain time (t1: minimum 2s):
▪ This connects the back-up power supply to the input terminals L1 and L3.
▪ This activates the input terminal CI1. Inverter goes into an evacuation operation mode and
inverter fault is cleared.
Control recognizes that the inverter is ready (no fault).
Control activates the drive ENABLE signal (input terminal EN) by activating the main
contactors (KPA and KPB).
Control applies the speed and direction command to the inverter.
▪ If the parameter 12.2-DIRECTION” is set as “BD: EASIEST DIR”:
◦ Inverter ignores the applied speed and direction commands and starts running the
motor in the optimum direction (easy direction) with a maximum speed limited with V4
speed.
▪ If the parameter “12.2-DIRECTION” is set as “BD: COMMAND DIR”:
◦ Inverter ignores only the applied speed command and starts running the motor in the
direction applied with a maximum speed limited with V4 speed.
Control deactivates the evacuation operation after the trip is completed with the following
sequence:
▪ Control releases the KKAK contactor:
◦ This disconnects the back-up power supply from the inverter.
◦ This deactivates the input terminal CI1. Inverter goes into a normal operation mode.
▪ Control reconnects the mains power to the inverter by activating the KSAK contactor after
a certain time (t2: minimum 1s).
Mains power failure
t1
t2
KSAK
KKAK
EN
UP/DWN
Vx (V0/V1/V2/V3)
AC supply
mode
Evacuation mode
AC supply
mode

Table of Contents