Probable Causes / Corrective Actions
The inverter output
current exceeded the
over current detection
level.
1- Because of the acceleration time of the elevator
is too short motor current may increase. Decrease
the acceleration parameter PA.
2- Check the V/f characteristics. Decrease Vmid
(Middle frequency voltage) and Vmin (Minimum
frequency voltage).
3- The motor being used has a capacity more than
Inverter's maximum motor capacity. Check the
Inverter's motor power.
The parameters of the
inverter are erased or
corrupted.
1- Change the parameters of the inverter to factory
defaults. Then reenter your configuration.
The motor overload
protection function
has operated based on
the internal electronic
thermal value.
1- Check the motor rated current.
2- Check the “Motor Setup - Thermal Mod”
parameter. The parameter may be too low.
The main supply
voltage L1, L2, L3
oscillates unusually.
1- The main supply voltage is too low.
2- An open-phase error occurred at the input
power supply.
3- A momentary power loss occurred.
4- The wiring terminals for the input power supply
are loose.
5- The voltage fluctuations in the input power
supply are too large.
A fault occurred
during auto tuning in
open loop mode. Auto
tune operation cannot
be completed.
1- Check motor connection. Motor connection
may not be done properly.
2- Motor contactor may not be switching. Be sure
that the motor contactor closes when inverter is
running.
The speed read from
encoder is too high.
1- Motor speed may be higher than the reference
speed. Check motor setup in the menu.
2- Compare the pulse number setting in the menu
“Motor Setup - Encoder Resolution” with the
encoder pulses and correct if necessary.
The encoder signals
oscillate unusually.
1- Check encoder connection and encoder voltage.
2- Check the connection between encoder and
motor.
3- If the encoder cable is not shielded, use a
shielded cable.
4- If the motor cable is not shielded, use a shielded
cable.
5- Encoder cable may be placed too close to motor
cable. Motor cable and encoder cable channels
should be separate. Minimum distance between
cables should be at least 10cm.
6- Encoder may be grounded at both the motor
side and inverter side. If the encoder is grounded
at motor side, disconnect the grounding at inverter
side.