Rev D CHP Max DC Power Supply 5-19
Regulatory Requirements (Note 4)
EN 300 386 V1.4.1
EN 55022, Class B
EN 55024
FCC CFR 47 Part 15 Class B
ICE S-003 Issue 4 Class B
UL60950 2nd Ed/CSA C22.2 number IEC 60950 and EN 60950
Notes:
1. Inrush current shall not trip a 15A mains external circuit breaker during a Hot Start condition. Hot Start occurs when a thermally stabilized power supply is
removed and immediately reinserted.
2. Inrush current shall not trip a 20A mains external circuit breaker during a Hot Start condition. Hot Start occurs when a thermally stabilized power supply is
removed and immediately reinserted.
3. When operating at 2C over the input operating range with a full rated output load.
4. All emissions tests must be passed in two configurations: two power supplies operating redundantly and a single power supply installed in a chassis
configured to provide maximum system load.
Table 5.6 CHP DC Power Supply Specifications (contd)
Characteristic Specification