Current limiter
See chapter 'Settings', under parameter Con - Current limiter to set the parameter. This parameter
must be set before any pan is placed on the hob or cooking zone activated.
WARNING!
Current limiter setting must be set according to your connection and circuit breakers by a
registered and qualified installer. Please read the safety regulations and the installation instructions
carefully.
NOTE!
Setting a lower value of the Current limiter parameter may cause a reduced performance of the
induction hob.
Voltage between phase and neutral conductors must be 220-240 V~. Voltage between phase
conductors must be 380-415 V~.
Power cord core cross sectional area should be at least 1,5 mm² for the following current limiter
settings which should be adjusted to your circuit breakers:
Number and cross section
of Power cord wires
Power cord
Type
Connection typeCurrent limiter
settings
5 x 1,5 mm²H05V2V2-F3 phases - 1 neutral3 x 16 A
5 x 1,5 mm²H05V2V2-F3 phases - 1 neutral3 x 13 A
5 x 1,5 mm²H05V2V2-F3 phases - 1 neutral3 x 10 A
5 x 1,5 mm²H05V2V2-F3 phases - 1 neutral3 x 06 A
4 x 1,5 mm²H05V2V2-F2 phases - 1 neutral2 x 16 A
4 x 1,5 mm²H05V2V2-F2 phases - 1 neutral2 x 13 A
4 x 1,5 mm²H05V2V2-F2 phases - 1 neutral2 x 10 A
4 x 1,5 mm²H05V2V2-F2 phases - 1 neutral2 x 06 A
5 x 1,5 mm²H05V2V2-F2 phases - 2 neutral (only for
NL)
2 x 16 A
3 x 6,0 mm²H05V2V2-F1 phase - 1 neutral1 x 40 A
3 x 6,0 mm²H05V2V2-F1 phase - 1 neutral1 x 35 A
3 x 4,0 mm²H05V2V2-F1 phase - 1 neutral1 x 32 A
3 x 4,0 mm²H05V2V2-F1 phase - 1 neutral1 x 25 A
3 x 2,5 mm²H05V2V2-F1 phase - 1 neutral1 x 20 A
3 x 1,5 mm²H05V2V2-F1 phase - 1 neutral1 x 16 A
68