Astraada DRV-24 frequency inverters Function Parameters
35
Detailed instruction of parameters
inverter will stop; otherwise, the inverter stops
in the time set by P01.24.
Setting range: 0.00~100.00s (only valid when
P01.16=1)
Terminal
running
protection
selection
when
powering
on
When the running command channel is the
terminal control, the system will detect the
state of the running terminal during powering
on.
0: The terminal running command is invalid
when powering on. Even the running command
is detected to be valid during powering on, the
inverter won’t run and the system keeps in the
protection state until the running command is
canceled and enabled again.
1: The terminal running command is valid when
powering on. If the running command is
detected to be valid during powering on, the
system will start the inverter automatically
after the initialization.
Note: This function should be selected with
cautions, or serious result may follow.
The running
frequency is
lower than
the lower
limit one
(valid if the
lower limit
frequency is
above 0)
This function code determines the running
state of the inverter when the set frequency is
lower than the lower-limit one.
0: Run at the lower-limit frequency
1: Stop
2: Hibernation
The inverter will coast to stop when the set
frequency is lower than the lower-limit one.if
the set frequency is above the lower limit one
again and it lasts for the time set by P01.20, the
inverter will come back to the running state
automatically.
Hibernation
restore
delay time
This function code determines the hibernation
delay time. When the running frequency of the
inverter is lower than the lower limit one, the
inverter will stop to stand by.
When the set frequency is above the lower
limit one again and it lasts for the time set by
P01.20, the inverter will run automatically.