gure 27 - Hydraulic unit manual bleeder valve
P
4.1.3 Volume of the heating system
You must maintain the minimum installation water
volume. Install a buer tank on the return from the
heating circuit in case the volume is lower than this
value. Where the system is tted with one or more
thermostatic valves, you must ensure that this minimum
water volume is able to circulate.
Theoretical volume in litres PER CIRCUIT (excl. HP)
Appliance
Mandatory
Fan-coil
Recommendation
Radiators
Recommendation
Heating-cooling oor
Alféa Extensa A.I. 5 23 12 2
Alféa Extensa A.I. 6 23 12 2
Alféa Extensa A.I. 8 36 33 15
Alféa Extensa A.I. 10 49 44 22
Alféa Extensa A.I. 13 55 50 25
Alféa Extensa A.I. 16 74 66 35
4.2 Filling and bleeding the installation
Check the pipe xings, tightness of the connectors and
the stability of the hydraulic unit.
Check the direction in which the water is circulating and
that all the valves are open.
Proceed to ll the installation.
Do not operate the circulation pump during lling. Open
all the drain valves in the installation and the bleeder
valve on the hydraulic unit (P) to expel the air contained
in the pipes.
Close the drain and bleeder valves and add water until
the pressure in the hydraulic circuit reaches 1 bar.
Check that the hydraulic circuit has been bled correctly.
Check there are no leaks.
After the "Commissioning", page 46 stage, and once the
machine has started, bleed the hydraulic unit again.
" Precise lling pressure is determined by the
water pressure in the installation.
Installation manual "1872 - EN" - 35 -
Alféa Extensa A.I. Heat Pump