14.2 Commissioning technical datasheet
Site Installer
Outdoor unit
Serial N
o
.
Hydraulic unit
Serial N
o
.
Model Model
Refrigerant type Refrigerant load Kg
Checks Operating voltage & current on outdoor unit
Compliance with positioning distances L/N V
Condensate evacuation correct
Electric connections / connections tightness L/E V
No GAS leaks (unit ID N
o
. : )
Installation refrigeration connection correct (length
m)
N/E V
Taken in operation when HOT
Compressor discharge temperature °C Icomp A
Liquid line temp. °C
}
}
}
Condensation
temperature
HP = bar °C Under-cooling °C
Tank water output temperature °C ΔCondensation Temp. °C
Tank water input temperature °C ΔSecondary Temp. °C
Evaporation temperature LP = bar °C
}
}
}
Suction Temp. °C Overheating °C
Battery air input temperature °C ΔEvaporation Temp. °C
Battery air output temperature °C ΔBattery Temp. °C
Hydraulic network on hydraulic unit
Secondary system
Underoor heating system
Circulation pump brand TypeLT Radiators
Fan coils
Domestic hot water; tank type
Estimated water volume of secondary system L
Options & accessories:
Electric backup kit Room sensor A59
Correct location of room sensor Wireless room sensor A75
2 circuit kit Wireless room sensor A78
Boiler connection kit
DHW kit
DetailsCooling kit
Control settings
Conguration type
Essential settings
Installation manual "1872 - EN"