- 93 -
Rated voltage 3ph line to line 400 V 480 V
Rated voltage 3ph line to line lower voltage (optional) 230 V -
Rated current 3ph 722 A 687 A
Rated current 3ph lower voltage (optional) 1255 A -
Performance class (acc.ISO 8528-5:1993) G2 G2
Single step load acceptance (0-PRP) 62% 72%
248 kW 329 kW
Frequency droop <5% <5%
isochronous isochronous
Fuel consumption at 0% load 8.9 kg/h 13.2 kg/h
Fuel consumption at 50% load 42.8 kg/h 53.2 kg/h
Fuel consumption at 75% load 62.6 kg/h 73.7 kg/h
Fuel consumption at full load (100%) 82.8 kg/h 100.4 kg/h
Specific fuel consumption at full load (100%) 0.207 kg/kWh 0.219 kg/kWh
Fuel autonomy at full load with standard tank 9.4 h 7.8 h
Max. oil consumption at full load 0.10 l/h 0.11 l/h
Maximum sound power level (LWA) measured according to
2000/14/EC OND (measured at 75% PRP load)
99 dB(A) 100 dB(A)
Maximum sound power level (LPA) measured according to
Atlas Copco
- 77 dB(A)
Useful capacity of fuel tank 905 l 905 l
Single step load capability (O-PRP) 100% 100%
380 kW 457 kW
Application data Mode of operation PRP PRP
Site land use land use
Operation single/parallel single/parallel
Start-up and control mode manual/automatic manual/automatic
Start-up time unspecified unspecified
Mobility/Config. acc. to ISO 8528-1:1993 transportable/D transportable/D
Mounting fully resilient fully resilient
Climatic exposure open air open air
Status of neutral earthed earthed