EasyManua.ls Logo

AUMA NORM Series - Position Transmitter Configuration; Potentiometer Setting

AUMA NORM Series
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13. Setting of the potentiometer (option)
– For remote indication –
.
Move valve to end position CLOSED.
.
Take off cover at switch compartment.
.
Pull off indicator disc.
.
Turn potentiometer (R) counter-clockwise until stop is felt. End position
CLOSED corresponds to 0 %, end position OPEN to 100 %.
.
Turn potentiometer (R) slightly back from the stop.
.
Perform fine-tuning of the zero point at external setting potentiometer (for
remote indication).
.
Press indicator disc on shaft and perform setting as described on page
12, clause 9.
.
Clean sealing faces at cover and housing; check whether O-ring is in good
condition. Apply a thin film of non-acidic grease to the sealing faces.
.
Fit and fasten switch compartment cover.
14. Setting of electronic position transmitter RWG (option)
– For remote indication or external control –
After mounting the part-turn actuator to the valve, check setting by measu-
ring the output current (see subclause 14.1 or 14.2) and re-adjust, if neces
-
sary.
13
Part-turn actuators SG 03.3 – SG 04.3
Operation instructions AUMA NORM
Figure H
R
Terminal plans KMS _ _ _ _ R _ /_ _
4-wire system
KMS _ _ _ _ Z _ /_ _
KMS _ _ _ _ Z _ /_ _
2-wire system
Output current I
a
0 – 20 mA, 4 – 20 mA 4 – 20 mA
Supply voltage U
v
24 V DC, ±15 %
smoothed
12 V DC + (I x R
B
),
max. 30 V
Max. input current I 25 mA at 20 mA
output current
20 mA
Max. load R
B
600 (Uv – 12 V) / 20 mA
Table 5: Technical data RWG 6020

Table of Contents

Related product manuals