Design Figure 23: Design principle with wall bracket
[1] Wall bracket
[2] Connecting cables
[3] Electrical connection of wall bracket (XM)
[4] Electrical connection of actuator (XA)
[5] Electrical connection/bus connection of controls (XK) - customer plug
Observe prior to
connection
●
Permissible length of connecting cables: max. 100 m.
●
If the actuator is equipped with a position transmitter (RWG): Connecting cables
must be available as shielded version.
●
Versions with potentiometer in the actuator are not suitable.
●
We recommend: AUMA cable set LSW1.
●
If the AUMA cable set is not used: Use suitable flexible and screened connecting
cables.
●
When using connecting cables, e.g. of the heater or switch, requiring direct wiring
from the actuator to the XK customer plug (XA-XM-XK, refer to wiring diagram),
these connecting cables must be subject to an insulation test in compliance
with EN 50178. Connecting cables of position transmitters (RWG, IWG, poten-
tiometer) do not belong to this group.They may not be subject to an insulation
test.
5.3.2 Parking frame
Application
Parking frame for safe storage of a disconnected plug.
For protection against touching the bare contacts and against environmental
influences.
Figure 24: Parking frame
26
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
Electrical connection AC 01.1 Intrusive Modbus RTU