For nominal voltage and 40 °C ambient temperature and an average load with running torque or modulating torque according to sepa-
rate technical data.The type of duty must not be exceeded.
1)
Technical data for limit and torque switches
2 x 10
6
startsMechanical lifetime
Silver plated contacts:
30 V AC/DCU min.
250 V AC/DCU max.
20 mAI min.
5 A at 250 V (resistive load)
3 A at 250 V (inductive load, cos phi = 0.6)
I max. AC current
0.4 A at 250 V (resistive load)
0.03 A at 250 V (inductive load, L/R = 3 µs)
7 A at 30 V (resistive load)
5 A at 30 V (inductive load, L/R = 3 µs)
I max. DC current
Gold plated contacts:
5 VU min.
30 VU max.
4 mAI min.
400 mAI max.
Technical data for blinker transmitter
10
7
startsMechanical lifetime
Silver plated contacts:
10 V AC/DCU min.
250 V AC/DCU max.
3 A at 250 V (resistive load)
2 A at 250 V (inductive load, cos phi ≈ 0.8)
I max. AC current
0.25 A at 250 V (resistive load)I max. DC current
12.2 Features and functions of actuator controls
For mains voltage and mains frequency, refer to name plates at the controls and the motor
Permissible variation of the nominal voltage: ±10 %
Permissible variation of the mains frequency: ±5 %
Power supply, mains frequency
Motor current consumption: Refer to motor name plate
Current consumption of the controls depending on the mains voltage:
100 to 120 V AC = max. 650 mA
208 to 240 V AC = max. 325 mA
380 to 500 V AC = max. 190 mA
Current consumption
24 V DC +20 %/–15 %
Current consumption: Basic version approx. 200 mA, with options up to 500 mA
External supply of the electro-
nics (option)
The controls are designed for the rated power of the motor, refer to motor name plateRated power
Category III according to IEC 60364-4–443Overvoltage category
Standard:
Reversing contactors (mechanically and electrically interlocked) for motor power up to power
class A1
Options:
●
Reversing contactors (mechanically and electrically interlocked) for motor power up to
power class A2
●
Thyristor unit for mains voltage up to 500 V AC (recommended for modulating actuators)
for AUMA power classes B1, B2 and B3
Switchgear
1) 2)
Via fieldbus interfaceControl
Via fieldbus interfaceOutput signals
63
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
AC 01.1 Intrusive Modbus RTU Technical data