7. Indications
7.1 Status indications in the display
The status indications in the display locally indicate the current operation states as
well as faults and warnings.
This section describes the indications for the operation states. Faults and warnings
are described in the <Fault indications and warning indications> chapter.
7.1.1 Status indication S0/S6 - operation
Information
For actuators equipped with process controllers, status indication S6 is displayed
instead of status indication S0 in selector switch position REMOTE.The description
below applies to both indications (S0 and S6).
Operation mode display
Line 1 indicates the current operation mode (LOCAL MODE, OFF, REMOTE MODE,
…).
LOCAL MODE S0
OPEN
E2 100 %
RUNNING OPEN
Operation command/set-
point display
Line 2 indicates currently incoming operation commands (OPEN, STOP, CLOSE)
or the setpoints E1 or E7 (for actuators equipped with positioner/process controller)
in % of the total travel.
LOCAL MODE S0
OPEN
E2 100 %
RUNNING OPEN
Valve position display
Line 3 indicates the valve position in % of the travel.This indication is only available
if the actuator is equipped with a position transmitter.
LOCAL MODE S0
OPEN
E2 100 %
RUNNING OPEN
0 % = Actuator is in end position CLOSED
100 % = Actuator is in end position OPEN
End position/running in-
dication
Line 4 indicates the current actuator status.
LOCAL MODE S0
OPEN
E2 100 %
RUNNING OPEN
Description of indications in line 4:
RUNNING OPEN
Actuator runs logically OPEN (remains set during operation pauses).
RUNNING CLOSE
Actuator runs logically CLOSE (remains set during operation pauses).
OPEN POSITION
34
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
Indications AC 01.1 Intrusive Modbus RTU