5.3.1.3. Motor connection compartment: close
Figure 35: Close motor connection compartment
[1] Cover
[2] Screws for cover
[3] O-ring
[4] Cable gland
1. Clean sealing faces of cover [1] and housing.
2. Check whether O-ring [3] is in good condition, replace if damaged.
3. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
4. Fit cover [1] and fasten screws [2] evenly crosswise.
38
SA 25.1 – SA 48.1/SAR 25.1 – SAR 30.1